INTECONT PLUS Weighfeeder Operation Manual
1: - Overview
1: - Overview
What Is The INTECONT :
INTECONT PLUS is designed as a measuring and evaluation system for
Belt Weighers
Solids Flow Meters
Mass Flow Meters
Mass Flow Feeders
Weighfeeders
Loss-in-weight Feeders
The system is supplied in 3 variants:
1.Without option card (standard)
2.With option card VFE 610V for additional input/outputs and printer
3.With option card for Fieldbus
VSS021V: Modbus/S5
VPB 020V: Profibus
VCB020V: DeviceNet
This manual applies to control systems equipped with a conveyor belt.
1. Weighfeeder Control fo feed rate via a belt speed
2. Belt weigher with controlled pre-feeder Control of feed rate via belt load
3. Belt weigher with constant load Control of belt load via belt speed
For Further Reading:
Fieldbus manual BVH2220
S5-RK512 (3964r) FH 458
Modbus (Comp) FH 525
Display:
Size : - 5 x 7 - dot matrix with 6 mm character height
Upper display left: running messages
right: set feed rate in kg/h or t/h
Lower display left: event messages
right: selectable feed rate, belt speed, etc.
The display can be changed over to American units.
LEDs:
2 green and 3 red LEDs
Green LEDs: Ready
Red LEDs: Error or limit value messages
Red LEDs: Error or limit value messages
Keyboard:
Some Definitions:
I - Feed rate in kg/h or t/h Material amount discharged from a conveyor belt per unit time
P - Feed rate setpoint in kg/h or t/h
Z - Amount fed in kg or t Amount fed = feed rate x feed time
V - Conveyor belt speed in m/s
Q - Belt load in kg/m Weight or material on one belt meter
Gravimetric: Controlled mode
Volumetric : Uncontrolled mode
Y - Controller output in mA
Measuring principle:
Belt load Q and speed V are continuously measured and multiplied with one another. The result is feed rate I used to determine the amount fed out.
I = Q 。 V 。 3600 I in kg/h
I - Feed rate in kg/h or t/h Material amount discharged from a conveyor belt per unit time
P - Feed rate setpoint in kg/h or t/h
Z - Amount fed in kg or t Amount fed = feed rate x feed time
V - Conveyor belt speed in m/s
Q - Belt load in kg/m Weight or material on one belt meter
Gravimetric: Controlled mode
Volumetric : Uncontrolled mode
Y - Controller output in mA
Measuring principle:
Belt load Q and speed V are continuously measured and multiplied with one another. The result is feed rate I used to determine the amount fed out.
I = Q 。 V 。 3600 I in kg/h
Q in kg/m
V in m/s
Measuring Technique:
➤ Precision AC voltage amplifier with continuous correction of zero point and range.
➤ Highly resolving analog-to-digital converter. The integrated method is designed to efficiently suppress mains voltage interferences.
➤ 16-bit microcontroller
➤ Unlimited storage of counter readings configuration and calibration data.
The schematic below shows all inputs and outputs.
L/C ➤ Load cell used to acquire belt load Q
D ➤ Speed transducer
S ➤ Belt circuit sensor for automatic belt influence compensation BIC (not always present)
M ➤ Drive motor
24 V ➤ Power supply
MIN ➤ Relay output for lower limit values
MAX ➤ Relay output for the upper limit value
ALARM ➤ Relay output for ALARM
DEV. ➤ Relay output for DEVIATION fault
START/STOP➤ Start / stop scale
ACK ➤ Acknowledge event message
SET ➤ Analog setpoint
SERIAL ➤ Printer and a host computer
ON ➤ Scale is active. Outputs for control of belt and pre-feeder drives, a connection of totalizing counter and analog display unit are available.
RELEASE ➤ Release
2: - Operation
Power ON
During power failure
all counter readings
counter pulses still to be output
preselected normal displays,
Service values,e.g. ON-time
are stored for an unlimited time.
The internal clock continues running for approx. 5days.
After power-up, an automatic display and lamp test is performed, followed by the display version number, then by normal displays.
Message E1
reports power failure.
The message can be configured as an ALARM or WARNING.
ALARM:
Red lamp
symbol E1 flash.
Acknowledge message before starting scale.
WARNING:
Signal lamp
remains dark,
symbol E1 does not flash.
No acknowledgment. Start scale manually or automatically.
Signal Lamps
MIN (red) MIN LIMIT VALUE
lit if feed rate limit value is exceeded down.
MAX (red) MIN LIMIT VALUE
lit if feed rate limit value is exceeded up.
READY: The two green signal lamps light and no Alarm is available.
Normal Display
Upper Display
Left Rotating point as running message.
Scale is started, amount fed out and feed rate are acquired.
In STOP state (point stands still) only belt load and belt speed are measured.
Special features in addition to running
message:
blank = Gravimetric mode
V = Volumetric mode
In start-up and clearance
modes, "V" flashes.
⏩ = Keyboard mode
If Keyboard and Volumetric modes are active at the same time, "V" is framed by keyboard symbol.
Right Effective setpoint P 1)
If "=" flashes, Simulation mode is active.
Lower Display
Left Event reported by an alphanumeric code, e .g. E1 for power failure.
Right Selectable display
Counter Z1 Z1 = 5000 kg
Counter Z2 Z2 = 6000 kg
Counter Z3 Z3 = 1000 kg
Feed rate I = 1000 kg/h
Feed rate IR = 50.00 % 2)
Belt load Q = 10.000 kg/m
Belt load Qr = 50.0 % 2)
Belt speed V = 0.0500 m/s
Deviation Xd = 0.10 % 2)
External setpoint Pe = 1000 kg/h 3)
Percental setpoint Pr = 50.00 % 4)
Batch displays Zb, ZI, ZD 5)
1) With belt weighers controlled for constant belt load, counter 1 is displayed in place of setpoint.
All setpoint inputs are omitted.
2) Related to the nominal value
3) If serial or analog setpoint is preselected
4) If a percental evaluation of serial or analog setpoint is preselected
5) See "Batching Mode".
Display formats and units of Z1, Z2, Z3, P, Pe and I can be selected separately.
V in m/s
Measuring Technique:
➤ Precision AC voltage amplifier with continuous correction of zero point and range.
➤ Highly resolving analog-to-digital converter. The integrated method is designed to efficiently suppress mains voltage interferences.
➤ 16-bit microcontroller
➤ Unlimited storage of counter readings configuration and calibration data.
The schematic below shows all inputs and outputs.
D ➤ Speed transducer
S ➤ Belt circuit sensor for automatic belt influence compensation BIC (not always present)
M ➤ Drive motor
24 V ➤ Power supply
MIN ➤ Relay output for lower limit values
MAX ➤ Relay output for the upper limit value
ALARM ➤ Relay output for ALARM
DEV. ➤ Relay output for DEVIATION fault
START/STOP➤ Start / stop scale
ACK ➤ Acknowledge event message
SET ➤ Analog setpoint
SERIAL ➤ Printer and a host computer
ON ➤ Scale is active. Outputs for control of belt and pre-feeder drives, a connection of totalizing counter and analog display unit are available.
RELEASE ➤ Release
2: - Operation
Power ON
During power failure
all counter readings
counter pulses still to be output
preselected normal displays,
Service values,e.g. ON-time
are stored for an unlimited time.
The internal clock continues running for approx. 5days.
After power-up, an automatic display and lamp test is performed, followed by the display version number, then by normal displays.
Message E1
reports power failure.
The message can be configured as an ALARM or WARNING.
ALARM:
symbol E1 flash.Acknowledge message before starting scale.
WARNING:
remains dark,symbol E1 does not flash.
No acknowledgment. Start scale manually or automatically.
Signal Lamps
lit if feed rate limit value is exceeded down.
MAX (red) MIN LIMIT VALUE
lit if feed rate limit value is exceeded up.
READY: The two green signal lamps light and no Alarm is available.
Normal Display
Upper Display
Left Rotating point as running message.
Scale is started, amount fed out and feed rate are acquired.
In STOP state (point stands still) only belt load and belt speed are measured.
Special features in addition to running
message:
blank = Gravimetric mode
V = Volumetric mode
In start-up and clearance
modes, "V" flashes.
⏩ = Keyboard mode
If Keyboard and Volumetric modes are active at the same time, "V" is framed by keyboard symbol.
Right Effective setpoint P 1)
If "=" flashes, Simulation mode is active.
Lower Display
Left Event reported by an alphanumeric code, e .g. E1 for power failure.
Right Selectable display
Counter Z2 Z2 = 6000 kg
Counter Z3 Z3 = 1000 kg
Feed rate I = 1000 kg/h
Feed rate IR = 50.00 % 2)
Belt load Q = 10.000 kg/m
Belt load Qr = 50.0 % 2)
Belt speed V = 0.0500 m/s
Deviation Xd = 0.10 % 2)
External setpoint Pe = 1000 kg/h 3)
Percental setpoint Pr = 50.00 % 4)
Batch displays Zb, ZI, ZD 5)
1) With belt weighers controlled for constant belt load, counter 1 is displayed in place of setpoint.
All setpoint inputs are omitted.
2) Related to the nominal value
3) If serial or analog setpoint is preselected
4) If a percental evaluation of serial or analog setpoint is preselected
5) See "Batching Mode".
Display formats and units of Z1, Z2, Z3, P, Pe and I can be selected separately.