SCHENCK PROCESS INTECONT PLUS Weighfeeder Operation Manual

               INTECONT PLUS Weighfeeder Operation Manual

                                            1: - Overview

What Is The INTECONT :

INTECONT PLUS is designed as a measuring and evaluation system for

        Belt Weighers
        Solids Flow Meters
        Mass Flow Meters
        Mass Flow Feeders
        Weighfeeders
        Loss-in-weight Feeders

The system is supplied in 3 variants:

1.Without option card (standard)
2.With option card VFE 610V for additional input/outputs and printer
3.With option card for Fieldbus 
    VSS021V: Modbus/S5
    VPB 020V: Profibus
    VCB020V: DeviceNet

This manual applies to control systems equipped with a conveyor belt.

1. Weighfeeder Control fo feed rate via a belt speed
2. Belt weigher with controlled pre-feeder Control of feed rate via belt load
3. Belt weigher with constant load Control of belt load via belt speed

For Further Reading:
Fieldbus manual        BVH2220
S5-RK512 (3964r)    FH 458 
Modbus (Comp)       FH 525


Display:

Size : - 5 x 7 - dot matrix with 6 mm character height

Upper display left: running messages
                     right: set feed rate in kg/h or t/h
Lower display left: event messages
                     right:  selectable feed rate, belt speed, etc.
The display can be changed over to American units.

LEDs:

2 green and 3 red LEDs

Green LEDs: Ready
Red    LEDs: Error or limit value messages

Keyboard:

Flexible membranes with tactile touch

Some Definitions:

I       -   Feed rate in kg/h or t/h Material amount discharged from a conveyor belt per unit time
P      -   Feed rate setpoint in kg/h or t/h
Z      -   Amount fed in kg or t Amount fed  = feed rate x feed time
V      -  Conveyor belt speed in m/s
Q      -  Belt load  in kg/m Weight or material on one belt meter
                 Gravimetric: Controlled mode
                 Volumetric : Uncontrolled mode
Y      -  Controller output in mA

Measuring principle:

Belt load Q and speed V are continuously measured and multiplied with one another. The result is feed rate I used to determine the amount fed out.

I = Q 。 V 。 3600     I   in kg/h
                                    Q  in kg/m
                                    V  in m/s

Measuring Technique:

➤  Precision AC voltage amplifier with continuous correction of zero point and range.
➤  Highly resolving analog-to-digital converter. The integrated method is designed to efficiently suppress mains voltage interferences.
➤ 16-bit microcontroller
➤ Unlimited storage of counter readings configuration and calibration data.

The schematic below shows all inputs and outputs.


L/C                ➤  Load cell used to acquire belt load Q
D                   ➤  Speed transducer
S                    ➤  Belt circuit sensor for automatic belt influence compensation BIC (not always                                      present)
M                  ➤  Drive motor
24 V              ➤   Power supply
MIN              ➤   Relay output for lower limit values
MAX            ➤   Relay output for the upper limit value
ALARM       ➤   Relay output for ALARM
DEV.             ➤   Relay output for DEVIATION fault
START/STOP➤  Start / stop scale
ACK             ➤   Acknowledge event message
SET              ➤   Analog setpoint
SERIAL       ➤   Printer and a host computer
ON               ➤   Scale is active. Outputs for control of belt and pre-feeder drives, a connection of                                  totalizing counter and analog display unit are available.
RELEASE   ➤   Release

                                             2: - Operation

Power ON

During power failure

            all counter readings
            counter pulses still to be output
            preselected normal displays,
            Service values,e.g. ON-time

are stored for an unlimited time.
The internal clock continues running for approx. 5days.

After power-up, an automatic display and lamp test is performed, followed by the display version number, then by normal displays.

Message E1

reports power failure.
The message can be configured as an ALARM or WARNING.

ALARM:
                                                  Red lamp symbol E1 flash.
                                                  Acknowledge message before starting scale.
WARNING:

                                                  Signal lamp remains dark,

                                                  symbol E1 does not flash.
                                                  No acknowledgment. Start scale manually or automatically.




Signal Lamps


                                          MIN           (red)       MIN LIMIT VALUE
                                                                            lit if feed rate limit value is exceeded down.
                                          MAX          (red)      MIN LIMIT VALUE
                                                                            lit if feed rate limit value is exceeded up.
READY:                                                             The two green signal lamps light and no Alarm is                                                                                    available.
Normal Display

Upper Display

 Left                          Rotating point as running message.
                                  Scale is started, amount fed out and feed rate are acquired.
                                  In STOP state (point stands still) only belt load and belt speed are measured.

                                  Special features in addition to running
                                  message:
                                  blank =      Gravimetric mode
                                     V    =      Volumetric mode
                                                     In start-up and clearance
                                                     modes, "V" flashes.
                                     ⏩    =       Keyboard mode
                                     If Keyboard and Volumetric modes are active at the same time, "V" is framed                                       by keyboard symbol.

Right                        Effective setpoint P        1)
                                 If  "=" flashes, Simulation mode is active.
Lower Display

Left                         Event reported by an alphanumeric code, e .g. E1 for power failure.
Right                       Selectable display
Counter Z1                   Z1  =   5000    kg
Counter Z2                   Z2  =   6000    kg
Counter Z3                   Z3  =   1000    kg
Feed rate                       I    =    1000    kg/h
Feed rate                       IR  =     50.00   %        2)
Belt load                       Q   =     10.000  kg/m
Belt load                       Qr  =     50.0     %        2)
Belt speed                     V   =     0.0500  m/s
Deviation                     Xd  =     0.10     %        2)
External setpoint          Pe  =      1000   kg/h     3)
Percental setpoint         Pr  =      50.00   %        4)
Batch displays              Zb, ZI, ZD                    5)

1) With belt weighers controlled for constant belt load, counter 1 is displayed in place of setpoint.
     All setpoint inputs are omitted.
2) Related to the nominal value
3) If serial or analog setpoint is preselected
4) If a percental evaluation of serial or analog setpoint is preselected
5) See "Batching Mode".

Display formats and units of Z1, Z2, Z3, P, Pe and I can be selected separately.